Zhejiang Dengli Electric Meter Co., Ltd.
Products
Contact Us
  • Contact Person : Mr. Yang Victor
  • Company Name : Zhejiang Dengli Electric Meter Co., Ltd.
  • Tel : 86-577-62711820
  • Fax : 86-577-62711967
  • Address : Zhejiang,Yueqing,Xirendang Industrial Zone, Liushi Town, Yueqing City, Zhejiang Province, 325604 China
  • Country/Region : China
  • Zip : 325604

Three phase inserting type kilowatt hour meter ( mechanical meter,electric meter,energy meter)

Three phase inserting type  kilowatt hour meter ( mechanical meter,electric meter,energy meter)
Product Detailed
Related Categories:Diesel Generators

Detailed Product Description


DEM141PK

INSERTING TYPE THREE PHASE FOUR WIRE ELECTROMECHANICAL ACTIVE ENERGY METER

 

Application

Model DEM141PK inserting type three phase four wire electromechanical active energy meter is a kind of new style three phase four wire active energy meter, it is on the basis of original D86 three phase electromechanical meter, and fully absorb new technologies about electromechanical meter from domestic and abroad. The meter completely accord with relevant technical requirements of class 1 or class 2 three phase active energy meter stipulated in international standard IEC 62053-11. It can accurate and directly measure 50Hz or 60Hz active energy consumption from three phase four wire AC electricity net, it is use for inserting installed on all kinds of panels of switchgear and distribution box. The meter has novel design, rational structure, and it can display total energy consumption by drum wheel mechanical register. It has following features: high overload, power loss, long-life, specious appearance, convenient installation, etc.

Functions and features

+  Inserting installed, the panel opening size: 152×234mm, the cover is made ABS

    engineering plastics molded overall which has a transparent glass window, the bottom of the

    meter and the terminal are also made of ABS engineering plastics molded overall. It has

    following features: good weatherability, high rigid, good insulation performance, etc.

+  The meter frame adopt aluminum molding with excellent mechanical strength, stable

    structure and anti-impact.

+  Voltage components and current components is used of double insulation structure, has

    good electrical characteristics.

+  Standard configuration the meter adopt double gem bearing, oriented bearing is made of

    lubrication graphite bush and stainless steel needle. It has following features: small abrasion

    and minimal friction, etc. May select magnetic thrust bearing (Product Configuration code is

    PC)

+  All kinds of error adjustment mechanism adopt no step shifting mechanism. The meter

    starting and creeping neednt to be adjust which is finished by anti-creeping hole of disc and

    convenient for adjusting by users.

+  Standard configuration 6 digits display by drum wheel mechanical register, may select 7

    digits display by drum wheel mechanical register (Product Configuration code is PO).

+  Standard configuration without the device which can prevent retrograde, may select add the

    function of prevent retrograde. (Please specified when ordering).

+  Three components measure three phase four wire active energy consumption. The accuracy

    class 1 or class 2 may select by users. Complying with standard IEC 62053-11. (Please

    specified when ordering).

+  Standard configuration use CT, type 48Z wiring for operation, may select PT & CT (Product

    Configuration code is PL), type 48Z wiring for operation.

+  Short terminals cover.

Technical parameters 

Model

Accuracy

Reference

Voltage(V)

Current

specifications(A)

Starting

current(A)

Insulation

performance

DEM141PK

Class 1

Class 2

3×127/220

3×230/400

CT/5A

0.02

0.025

AC voltage 4kv for 1 minute,

1.2/50us  waveform pulse voltage 6kv

* If you need different reference voltage or current specification, please advisorse us.

Outer and mount dimension

160x158x240 mm

Wiring diagram (Type 48Z)

 

Terminals

Note

Terminals

Note

1

L1 phase line CT inlet

9

L1 phase line CT outgoing

3

L1 phase line CT outgoing

2

L1 phase line

4

L2 phase line CT inlet

5

L2 phase line

6

L2 phase line CT outgoing

8

L3 phase line

7

L3 phase line CT inlet

10

Dont use